Measuring Technology
EA16 - Measuring Display Unit 3,5" Touch LCD
- Monitoring of the room parameters in cleanrooms
- Sensitive touch display with a very high contrast and an enormous luminosity
- Easy-to-use touch display even when wearing gloves or using touch pens, etc.
- Visualization of up to four measurements simultaneously
- Data logging on secured SD card
- Parametrization via mini USB port
- Visualization of the measurement value curves directly on the device
- Warning messages in plain text
- Designation of the unit on the display freely selectable for easy mapping
- Communication via standard analog signals and other optional interfaces
- Four freely programmable switching contacts (different channels can be combined)
- Various color profiles can be selected for better usability
DE24 - Room Pressure Transmitter / Display
- Capacitive low-pressure sensor
- Long-term stable without recalibration
- High repeatability
- LC display with colour change of backlighting as clean room signal light
- User prompt in clear text
- In-situ calibration or adjustment
- Integrated control unit / Zeroing, calibration and setting without PC
- Password-protected to prevent unauthorised access
- Industry standard analogue output
- Measuring ranges:
unidirectional: 0...25 Pa to 0...1000 Pa bidirectional: ± 25 Pa to ± 100 Pa - Max. static pressure up to 100 kPa
- Output signal transmitter: 0...10 V, 0...20 mA, 4...20 mA, 3-wire
- Output signal contacts: 2 independent programmable solid state relays
- Operating voltage: 24 V DC/AC (20...32 V)
- Protection class IP65 (front panel and keypad)
FT61 - Measuring Device for Humidity / Temperature
- Capacitive humidity sensor
- Long-term stable without recalibration
- High repeatability
- LC display with colour change of backlighting as clean room signal light
- User prompt in clear text
- In-situ calibration or adjustment
- Integrated control unit / Zeroing, calibration and setting without PC
- Password-protected to prevent unauthorised access
- Industry standard analogue output
- Measuring ranges:
Humidity: 0 ... 100 % r.H., ± 3 % Temperature: - 40 ... + 100 °C, ± 0.5 °C - Interface Sensor -> Indicator: I²C Bus
- Output signal transmitter: 0...10 V, 0...20 mA, 4...20 mA, 3-wire
- Output signal contacts: 2 independent programmable solid state relays
- Operating voltage: 24 V DC/AC (20...32 V)
- Protection class IP65 (front panel and keypad)
EA14A - Universal Display
- Long-term stable without recalibration
- High repeatability
- LC display with colour change of backlighting as clean room signal light
- User prompt in clear text
- In-situ calibration or adjustment
- Integrated control unit / Zeroing, calibration and setting without PC
- Password-protected to prevent unauthorised access
- Industry standard analogue output
- Measuring ranges: freely definable areas and units
- Input signal display: 0...10 V, 0...20 mA, 4...20 mA, 3-wire
- Output signal transmitter: 0...10 V, 0...20 mA, 4...20 mA, 3-wire
- Output signal contacts: 2 independent programmable solid state relays
- Operating voltage: 24 V DC/AC (20...32 V)
- Protection class IP65 (front panel and keypad)
TW68 - Compact Resistance Thermometer with Miniature Head Transmitter
- Pt100 4-wire
- Class B as standard, Class A, 1/3 or 1/10 DIN upon request
- Integrated, precise 2-wire miniature head transmitter
- High degree of repetition accuracy
- Integration into wall mounting panels
- In-situ calibration
- Measuring ranges: programmable between -50 and +200 °C
- Output signal transmitter: 4...20 mA, 2-wire
- Operating voltage: 24 V DC
- Protection class IP65